The issue of voltage testing for high and low voltage switchgear has been a long-standing concern affecting electrical safety in production. Currently promoted fully enclosed "five-prevention" switchgear features mechanical "five-prevention" interlocking devices, which cannot meet the safety regulation requirement of "test for voltage first, then apply grounding wire." This is because, when carrying out power-off operations, it is necessary to verify that the equipment is de-energized before closing the grounding switch. However, fully enclosed high and low voltage switchgear is completely sealed, and according to normal operating procedures, it is impossible to test the equipment using a portable high-voltage tester. As a result, methods for forcibly unlocking and opening the switchgear doors for voltage testing have emerged.
In high and low voltage switchgear, high-voltage live display devices using neon lamps as indicators are widely used. After long-term operation, a high failure rate is observed, with many neon bulbs being damaged.
To address this flaw, a neon lamp operation/enclosure switch has been installed on live display devices. Normally, this switch is in the off position, temporarily disabling all high-voltage live display devices. This approach, however, eliminates the function of the high-voltage live display devices to monitor whether the circuit side is energized.